AIRMASTER Q1

AIRMASTER Q1 中文菜单快速查询 E15
此文档可以帮助您快速查询Q1控制器的菜单功能,使操作时更方便,快捷。          
Thu, 18 Feb, 2016 at 7:47 AM
Does the Airmaster ISC 'timer' feature reset following a power outage?
Airmaster products that feature ISC (Internal System Control) will remember the 'timer' state prior to the power outage.  When supply power is ret...
Wed, 24 Feb, 2016 at 5:53 PM
What is the default value of the temperature rise fault in the standard Q1 software?
Q: What is the default value of the temperature rise fault in the standard Q1 software? A: The default is set to 1.0°C (P17.02.01) over 10 seconds (...
Tue, 1 Mar, 2016 at 6:13 PM
Which languages are supported by the Airmaster Q1?
The Airmaster Q1 currently supports 22 languages: ENG     =>        ENGLISH BEL      =>        BELARUSIAN BRA     =>        BRAZILIAN C...
Wed, 16 Mar, 2016 at 4:57 PM
How can a user account be added or changed on an Airmaster Q1?
Anybody who has the active access code to log in as the ADMIN user (this code can be changed by ADMIN), can change settings for the ADMIN himself or the o...
Wed, 16 Mar, 2016 at 5:50 PM
How to connect & configure an Airmaster Q1 controller for Metacentre Master Control
Here you can download detailed instructions on how to set up your Airmaster Q1 controller for remote load/offload control by a Metacentre Master Controlle...
Wed, 3 Aug, 2016 at 3:07 PM
How to set up Q1 for ISC (Master/Slave)
This document describes how to connect and configure 2 Q1 controllers for Master/Slave control (ISC). Also available for download are the commiss...
Thu, 4 Aug, 2016 at 3:49 PM
I have changed the ISC rotation interval (P80.04) but the controller doesn't seem to apply the new setting.
ISC Sequencing - Rotation Interval Q : I have changed the ISC rotation interval time (P80.04) but the controller doesn’t seem t...
Fri, 7 Oct, 2016 at 1:42 PM
What do I need to establish Modbus communication with an Airmaster controller?
Modbus communication with an Airmaster controller. Q:        What do I need to establish Modbus communication with an Airmaster controller? A:        F...
Mon, 12 Dec, 2016 at 2:55 PM
When will the error code E0084 be generated?
Q : When will the error code E0084 be generated? A : E0084 is generated whenever the measured current for the main motor is below 20% of the nominal rated ...
Fri, 27 Jan, 2017 at 10:38 AM