Troubleshooting E:0821 how to find the cause of the error.
Try to reset the controller's E:0821 Short circuit fault by pressing the 'reset' button. If the fault does not clear (even shortly) after pressing the reset button, check if there is an electic leakage with the metal cover. If the fault does clear after pressing the reset button, check the incoming power supply voltage. If the power supply is different than the requested (24±15%), E:0821 will also be triggered.
- Remove both AI and DI connectors to see if the short circuit error disappears after pressing the reset button. If the fault goes away, identify if it is caused by the AI or the DI.
- Remove AI connector, keep DI connector. Does the short circuit error disappear?
- Remove DI connector, keep AI connector. Does the short circuit error disappear?
- After you identify if it's DI or AI, measure the voltage on each input with a multimeter. To identify the short circuit. You can find some examples below:
- Analog input 3: measure between X03 C-ANA3 and GND. (=5V or 24V)
- Analog input 1: measure between X03 C-ANA1 and GND (=24V)
- Digital input: measure between X02 C-DI and GND (=24V)
- Take a look at the display of the controller. If the delivery/sump/temperature (or any other AI) reading is missing, it can indicate that one of the AI's has a short circuit.
- The common (C-XXXX) is the pin who supplies voltage. So always measure between the common pin and GND.
The controller is broken if error E:0821 does not clear after considering the above steps.
Related Articles
Q-series error codes shortly explained
Now and then a software feature is developed and added to a generic software version. When new functions are added, often there are some error codes associated with it. It is possible that not all fault codes are enlisted in the Q-series ...
Error codes explained
While using ControlsStudio (CS) you may encounter one of the following error codes. What they mean exactly, and what you can do to resolve them, is described below. Feature access denied (H0005) CS uses different profiles. Each profile has access to ...
When will the error code E0084 be generated?
Q : When will the error code E0084 be generated? A : E0084 is generated whenever the measured current for the main motor is below 20% of the nominal rated current (P14.03) for over 10 seconds. We do not generate this error if VSD is used. So we only ...
Link error: Something went wrong with the connection to the controller
This article explains what you can check when the 'link error' appears. Check the configured protocol parameters of the communications port you are connected to. Terminal X04 for the Q1 and Q2 controllers. Terminal X02 for the FIT and FORM ...
Some common errors and how to solve them (Q-controller)
1. The machine does not start efter pressing the local start button on the controller display. Are there any start inhibits? Displayed by a S: error code. S:0133 - Air TEMP low INH. Air temperature low start inhibit S:3500 - Start inhibit (operator ...