ISC Sequencing - Rotation Interval
Q : I have changed the ISC rotation interval time (P80.04) but the controller doesn’t seem to apply the new setting (e.g. changed to 50 hrs but the sequence rotation happened after less than 24 hours).
A : Please note the following : The Q1 controller will not accept the new setting immediately when you change the ISC rotation interval time. Instead, it will ‘finish’ the sequence rotation that was last applied (e.g. P80.04 was set to 24hrs and has now been changed to 50 hrs. The Q1 controller will finish the 24hrs rotation it was in before it applies the new rotation time interval (50 hrs))
If you want the Q1 controller to apply the new rotation interval (In our example : 50 hrs), follow following steps :