Additional information for parameter "Restart Reminder"

Additional information for parameter "Restart Reminder"

P12.24 Restart Reminder


Restart reminder is a selection for information at power up. If at the moment of power down, there is an active immediate shutdown condition, there are 3 ways of starting up.

You switch this selection OFF and nothing happens.

When set to WARNING ALARM, a warning A:2826 will be generated at power on, suggesting that at power down something was wrong and you may want to check the error log to see what happened.

When set to IMM STOP ALARM, an immediate shutdown E:2826 condition will be flagged at power on, making it impossible for the compressor to start without someone resetting the error. The idea behind this is that someone should check what happened, before resetting the error and starting the machine.